Blog

Electric infrared underfloor heating: two systems

ComfortScrim at 12–48 V and SafeTech EGS at mains voltage: build-up, output, where each belongs, the trade-offs, and whether a heated floor is safe.

ComfortScrim laid across a villa floor, taped down and awaiting the levelling compound

We supply two electric infrared underfloor heating systems. ComfortScrim runs at 12 to 48 V from a central power supply and goes into the levelling compound. SafeTech EGS runs at 110 to 240 V straight off a circuit and comes as discrete pre-cabled heaters. Both are full-surface carbon fibre, both add a few millimetres, and both disappear under the finish.

They are not interchangeable. The choice is made by the floor finish, by which trades are already booked, and by whether the building has a sensible place to put a power supply. This article sets out what each one is, where it belongs, what it costs you in return, and what makes a heated floor safe to bury under a room.

Carbon fibre against heating cable

A conventional electric floor is a resistance cable laid in loops at a fixed spacing. All the heat for the room leaves through the surface area of that cable, which is small, so the cable runs hot — typically well above 60 °C — and the screed above it has to spread that heat sideways before any of it reaches the room. The spacing has to be right, the depth has to be right, and damage anywhere along the run is concentrated in one place.

A carbon-fibre element covers the whole floor area instead of a fraction of it. The same room output is spread across roughly ten times the emitting surface, so the element runs at a much lower temperature, and the heat travels upward as far infrared rather than sideways through the slab. Practical consequences: a shallower build-up, a faster response, no strips of floor that are warmer than others, and no single conductor carrying the whole load.

The lower operating temperature is also why the safety question is answered by construction rather than by thermal cut-outs alone. Nothing in the floor is hot enough to be a hazard on its own. What matters is keeping water away from the conductor and giving any fault somewhere to go.

The two systems at a glance

ComfortScrim floorSafeTech EGS floor
Voltage12 to 48 V, from the Multi Zone Power Supply110 to 240 V AC, direct to circuit
Supplied asRoll, 600 and 900 mm wide, cut to the drawingDiscrete heaters, made to length
Build-up2 to 3 mm in levelling compound or adhesiveAbout 2 mm dry, or embedded up to 5 cm
Output80 to 220 W/m²80 to 220 W/m²
Needs a power supplyYesNo
CertificationCE, UKCACE, UKCA, tested to UL 2683
Typical useBathrooms, wet rooms, buildings with PV or batteryFloating and dry finishes, tiled and screeded floors

ComfortScrim: low voltage under the levelling compound

ComfortScrim is the 0.4 mm element we also install behind plaster on walls and ceilings. On a floor it is rolled out across the slab, taped down and embedded in the levelling compound or tile adhesive that was going down anyway. It adds 2 to 3 mm. Rolls come in 600 and 900 mm widths and are cut to the layout drawing before delivery.

Power comes from a Multi Zone Power Supply at 12 to 48 V, one zone per room. This is safety extra-low voltage, which is the reason we specify it for bathrooms and wet rooms without further discussion: at those voltages the system is not capable of delivering a dangerous shock, whatever happens to the floor above it.

Carbon fibre floor film laid in bays across a terrace, copper bus bars along each edge, before the screed

Element laid out in bays with the bus bars run along each edge, before the screed goes down. Bursa, Türkiye.

In its favour. The thinnest build-up of anything we make, so it suits renovation where floor levels are fixed at doorways and thresholds. Safety extra-low voltage removes the wet-room argument entirely. A 48 V DC element takes power from a battery without an inverter, which matters if the building has solar and storage. And because walls and ceilings run on the same supply and the same zones, a whole-house scheme can be controlled as one system.

Against it. The power supply is real equipment that needs a location, a budget line and ventilation — a cupboard, a utility room, a plant space. Low voltage also means high current for the same power, so conductor sizing and run lengths matter and the supply has to sit reasonably close to the zones it feeds; a long thin run wastes power as heat in the cable. The rolls are cut to a drawing, which keeps decisions off site but also means the layout is settled before delivery. If the room changes after the kit ships, the kit is wrong.

SafeTech EGS: mains voltage in discrete heaters

SafeTech EGS runs straight off a 110 to 240 V circuit. There is no power supply and no transformer, so nothing has to be housed and no low-voltage distribution has to be designed.

It is supplied as individual heaters rather than a roll. Each is made to length — 600 or 900 mm wide, one to three metres long, according to the wattage density specified for the room — fully encapsulated, pre-cabled, and joined to the next through an IP68 connector. A floor is laid out and connected in one pass, with no cutting and no wiring decisions on site.

SafeTech EGS heaters laid out across an office floor with their connector cabling run between them

Discrete EGS heaters set out and daisy-chained to the design plan, Jinan.

Because it is a mains-voltage product sitting inside a floor, the encapsulation does the work. It comes in two thicknesses, and specifying the wrong one is the error we correct most often.

Thick overmoulding, for wet embedding

The heavier encapsulation is for tile adhesive, levelling compound and screed. It withstands the trowel and the weight of the screed above it, at any depth from a few millimetres up to 5 cm. Specify it for tile, stone, resin and screeded floors. If a wet trade is coming to the room in any case, this is almost always the right choice.

Thin overmoulding, for dry and floating floors

The thin version adds about 2 mm and is intended for floors that never get wet: laminate, engineered wood, click vinyl. The heater is laid on the underlayment and the finish goes straight over the top. Each element carries up to 5 m of cable back to a distribution box.

The thin-overmoulded SafeTech EGS heater with its cable tail, floor sensor and thermostat

The thin-overmoulded kit: heater, cable tail, floor sensor and thermostat.

Do not put the thin version under screed. It is not built for the trowel, and it is designed for two millimetres under a floating floor rather than fifty under a wet one. Where the finish is not yet decided, specify thick.

In its favour. No power supply to house, no transformer, and connection by a normal circuit means an ordinary electrician can complete the work. The plug-and-play chain goes down faster than rolls once the floor area gets large, which is why we specify it on open-plan commercial work. It is tested to UL 2683, the North American standard written for heating elements of this type. And the two overmouldings between them cover wet and dry construction, so one product serves most finishes.

Against it. Mains voltage inside a floor requires RCD protection and a competent electrician, which is not a burden but is not optional either. The heaters are made to length, so the layout is fixed when the order is placed — there is no trimming a heater to fit a changed alcove. Only elements below 140 W/m² are UL conforming, so North American projects are specified below that limit and given greater coverage to reach the same room temperature. Where the element is embedded in screed the build-up is deeper than ComfortScrim’s, which can matter at a threshold.

How the layers stack up

Both systems sit directly beneath the finish rather than deep in a slab, with insulation board underneath to push output upward instead of into the structure. That short distance between element and surface is what gives the floor a response measured in minutes.

Wet installation

Element embedded in levelling compound
Floor finish Tile, stone or wood Adhesive bed 3–5 mm · tile, stone or wood Levelling compound 2–3 cm Heating element SafeTech EGS, thick overmoulding · or ComfortScrim Insulation board 20 mm Levelled base layer Existing substrate Top Base

Dry installation

Element laid under a floating finish
Floor finish Wooden planks, direct or over a thin compound Adhesive bed 3 mm · tile, stone or bonded wood Heating element SafeTech EGS, thin overmoulding · or ComfortScrim Underlayment 4–6 mm Levelling compound Over the base Levelled base layer Existing substrate Top Base

Both build-ups work with low-voltage ComfortScrim and with mains-voltage SafeTech EGS. Which one you use comes down to the finish you have chosen and to whether wet trades are coming to the room anyway. A floating finish needs no adhesive bed.

Is a heated floor safe?

Voltage is the first answer and construction is the rest of it.

  • Full-surface grounding. An aluminium layer runs across the entire element rather than along a bonding strip, so a fault anywhere in the element meets a grounded plane immediately above or below it. UL 2683 requires 75% coverage; ours covers the whole surface.
  • UL 2683. SafeTech EGS is tested to it. It is the North American standard written specifically for heating elements of this type, and it is not a self-declaration.
  • Insulation resistance above 500 MΩ. Factory tested, measured at 968 MΩ. This is the figure that confirms the conductor and everything around it stay properly separated.
  • IP68 connections. The connectors between heaters are rated for continuous immersion, which is what is required of something buried under a wet screed.
  • Flame-retardant construction and an overheat cut-out. The element cannot run away, and where conditions above it change — a rug, a mattress, a stack of boxes — the cut-out acts before the temperature does.
  • Safety extra-low voltage on ComfortScrim. At 12 to 48 V the system cannot deliver a harmful shock in the first place.

The tests behind those claims are filmed: the element held in direct flame, submerged and energised, grounded, high-potential tested, then flexed and punctured to establish what it takes to break it.

SafeTech · five tests every element passes

Safety is not a claim we make about the system. It is a set of tests the element itself passes, filmed in our own laboratory, and the certifications that follow from them.

  • Direct flame test

    Fire resistance

    The element is held in direct flame. It does not sustain a flame or propagate one along the film.

  • Submerged and energised

    Water immersion

    Submerged and energised. Zero moisture absorption, which is what lets the element go into a bathroom or a wet room.

  • Grounding test

    Full-surface grounding

    A grounded conductive layer across the whole element rather than a wire with a sheath, so a fault anywhere on the surface is carried to earth.

  • HIPOT test

    High-potential test

    Every element is HIPOT tested before it leaves the factory, at multiples of its working voltage.

  • Flex and puncture test

    Structural integrity

    Flexed, punctured and pulled. A damaged area is spliced in place and re-tested rather than replaced.

What both systems share, including the drawbacks

Neither product is a heat store. Both respond in minutes and cool in minutes, which suits rooms heated when they are occupied and does not suit a strategy built around overnight storage tariffs. Both need insulation below the element; without it a share of the output goes into the slab and never reaches the room. And both are electric resistance heating, so while every kilowatt-hour drawn becomes heat in the room, the running cost follows the electricity price, which is higher per unit than gas in most markets. Whether that nets out in your favour depends on the building, the tariff and how the rooms are used, which is what a layout and a heat loss calculation are for.

Choosing between them

  • Bathrooms and wet rooms — ComfortScrim. Safety extra-low voltage, and the compound is going down regardless.
  • Buildings with PV or battery — ComfortScrim at 48 V, taking DC from storage without an inverter.
  • Laminate, engineered wood, click vinyl — SafeTech EGS, thin. No wet trade required.
  • Tile, stone, resin, screed — SafeTech EGS, thick.
  • Large open floors — SafeTech EGS. Plug-and-play modules go down faster than rolls at scale.
  • Walls or ceilings heated in the same project — ComfortScrim, so everything runs on one supply and one set of zones.

MAPEI publish a build-up recommendation for laying the element with their primers, levelling compounds and adhesives, covering each substrate and each floor finish. It is on the floor heating page alongside the datasheets.

Send us the floor plan and the construction and we will tell you which system we would specify and why, with a room-by-room heat loss behind it. Get a layout for your plan, or read how infrared heating works for the physics.

Two further articles go deeper on safety: are infrared heaters safe covers the general case, and is far infrared heating safe deals with the radiation itself.

Send us a floor plan.We will send back a heating system.

Project data, drawings or CAD files in. A room-by-room heat loss, element layout and priced proposal out. No obligation.